You are here

1-Wire UNI

  • Pt-100 based low temperatures sensor with 1-Wire UNI output. Contains a Pt-100 temperature probe (-190 to +150°C, PTFE covered cable 2m,Pt100/B) and a 1-Wire UNI converter (Converter 2xPt100 1W-UNI). Second Pt-100 or Pt-1000 temperature probe can be connected.
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    ± 0.3 °C in range from - 50°C to +150 °C
    ± 0.6 °C in range from - 190°C to -50 °C
    0.10
    PT100/PT1000
    -190
    150
    Temperature
    Temperature
    °C
    8
  • Pt-100 based temperature sensor with 1-Wire UNI output. It contains a Pt-100 probe (-50°C to 200°C, Pt100/A, 2m silicon cable) and a 1-Wire UNI converter (Converter 2xPt100 1W-UNI). The second Pt-100 or Pt-1000 probe can be connected.
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    ± 0.3 °C in range from - 50°C to +200 °C
    0.10
    PT100/PT1000
    -50
    200
    Temperature
    Temperature
    °C
    8
  • Electrically isolated voltage sensor for up to 60VDC with 1Wire-UNI output. Typical applications include measuring voltage at industrial sensors (0-10V) or battery voltage. Frequently used for 48 volt power supply measurement in telecommunications (48V standard). Voltage can be monitored over LAN ( Poseidon2 or GSM ( Ares ). Sensor is equipped with 8-points calibrating table/curve to set measured output appropriate to related industrial sensor. The calibration process is supported by 1W-UNI USB...
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    2% / 25°C
    0.10
    Converter
    0
    60
    Voltage
    Voltage
    V
    1 YES 8
  • Isolated DC current sensor for the 1Wire-UNI bus. Sensor for measuring currents in the 0–20mA range. It is typically used to connect a industrial probe with 4–20mA output - 2wire current loop ("sink"type). Sensor current output is processed in Poseidon2 or Ares units to ber accesible via LAN or GSM. Sensor is equipped with 8-points calibrating table/curve to set measured output appropriate to related industrial sensor. The calibration process is supported by 1W-UNI USB calibrator .USB dongle...
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    ± 2% of the whole range
    0.10
    Converter
    4
    20
    Current
    Current
    mA
    1 NO 8
  • The sensor is designed for measuring of AC voltage in the range 100 - 250V AC. The 1W-uni output bus is isolated. Typical usage of sensor contains voltage variation or drop out detections. Measured values are processed by Poseidon2 (LAN) or Ares (GSM) units, to be accessible for monitoring apps.
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    5%
    1.00
    Converter
    0
    250
    Voltage
    Voltage
    V
    8
  • Isolated DC current sensor for the 1Wire-UNI bus. Sensor for measuring currents in the 0–20mA range. It is typically used to connect a industrial probe with 4–20mA output - 4wire with discrete power supply (e.g. to measure the fuel level in a tank). Sensor current output is processed in Poseidon2 or Ares units to ber accesible via LAN or GSM. Sensor is equipped with 8-points calibrating table/curve to set measured output appropriate to related industrial sensor. The calibration process is...
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    ± 2% of the whole range
    0.10
    Converter
    0
    20
    Current
    Current
    mA
    1 YES 8
  • External Relay output 1W-UNI module allows to expand Ares 12 and Ares 14 functionality by remote control of up to 4 relay outputs with a dry contact (NO/NC) up to 50V / 1A load. Relay output 1W-UNI for Ares allows manula external system switching via SMS or SensDesk application. any contact can be switched automatically upon alarm detected by sensor, connected to Ares unit. Set can be used as thermostat, automatic switch of backup units, optical or accoustic alarms, etc. The Relay uotput 1W-UNI...
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Measure OBSOLETE_Unit
    Switch
    switch
    NO None
  • Simple light intensity sensor for indoor use. The sensor is designed for use with Poseidon and Ares devices via 1-Wire UNI bus (RJ11).
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    ±10%
    1.00
    Semiconductor
    0
    100
    Illuminance
    Illuminance
    %
    1 NO None
  • A universal water flood sensor detects flood occurence by soak-detecting cable. Soaking or interrupting of cable cause switching of relay contact (NO/NC) .Sensing cable detects small quantity of water or other liquid. The „ WLD sensing cable A “ is supplied in lenght from 0,4 to 85 m. It can be connected with extension cable with up to 100 m lenght. HWg-WLD Relay can be used separately with 12V power supply and relay output or as sensor with Poseidon 2 connected via 1Wire UNI bus.
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Technology Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    Converter
    1
    WLD
    Weather leak detection (WLD)
    WLD
    1 YES None
  • Simple sensor o flooding or water level detects water amont 4 points on detector body (1D water detection). Sensor can be placed on wall or floor with dielectrict surface. Connects to Ares or Poseidon2 using the 1-Wire UNI (RJ11) interface.
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    OBSOLETE_Measure Measure OBSOLETE_Unit
    Switch
    Weather leak detection (WLD)
    WLD
  • Expansion module for connection of 4 dry contact inputs to Ares and Poseidon units. Connect another button, door contact, smoke detector etc. to the 1-Wire UNI bus (RJ11).
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Technology OBSOLETE_Measure Measure OBSOLETE_Unit
    Expander
    Switch
    Switch
    switch
    4 NO
  • Double converter to connect two Pt-100 and Pt-1000 probes to 1-Wire UNI (RJ11). One or two external temperature probes can be monitored over LAN Poseidon2 ) and GSM ( Ares ) Typical applications include measuring extreme temperatures in furnaces, coolers, engines, etc.
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    ± 0.3 °C in range from - 200°C to +650 °C
    ± 0.6 °C in range from - 200°C to +850 °C
    0.10
    PT100/PT1000
    -200
    850
    Temperature
    Temperature
    °C
    NO 8
  • 30A Current probe 1W-UNI 2 is a sensor for indirect single-phase measurement of AC current up to 30A without cutting the wire. The split-core current transducer can be opened in order to insert a line wire. The sensor is suitable for monitoring power consumption of racks, BTS’s or server rooms. Sensor is suitable for Poseidon and, Ares product family.
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    ± 2.0
    0.10
    Converter
    0
    30
    Current
    Current
    A
    1 YES 8
  • 100A (30A) DC Current probe 1W-UNI is set of shunt and converter that can measure DC current up to 100A (30A). The shunt is connected directly (interrupting the wire) into measured circuit. The DC current is measured in both directions (distinguished by the sign). The 1W-UNI output can be connected to Poseidon2 or Ares devices. Together with one of these units, the current probe can serve early warning f overload or current direction change (charge/discharge). The probe is suitable for input...
    Measurment OBSOLETE_Sensors number Galvanic isolation Units Converter Calibrated Points Consumption
    Accuracy Resolution Technology Range min Range max OBSOLETE_Measure Measure OBSOLETE_Unit
    2%
    0.10
    Resistor
    0
    100
    30
    Current
    Current
    A
    NO 8